Incrementing function of the LossOfSoC counter cannot be ensured in case of optional nodes (eliminated from V1.10 onwards)

Eliminated from:
E94AYCEP Communication module Firmware V1.10 in CN mode (Control Node)
E94AYCEC Communication module Firmware V1.10



Which products are affected?
E94AYCEP communication module Firmware V1.05 in CN mode (Control Node)
E94AYCEC communication module Firmware V1.05

What happens?
The incrementing function of the LossOfSoC error counter (Lenze code C13127 / C14127) is not always executed when a Powerlink communication error has appeared.

When does the problem occur?
The problem occurs if there are communication problems on the Powerlink network.

Possible diagnostics?
None.

Short-term measures/recommendations?
None.

Evaluation:
From Firmware V1.10 onwards the incrementing function of the  LossOf SoC error counter works correctly whenever a Powerlink communication problem occurs.