bPosDone is set to FALSE if bPosStop and S profile are used (eliminated from V5.0 onwards)
Eliminated from:
HighLine with firmware version V05.01 or higher
Behaviour of the new version?
The bPosDone status bit of the "Table positioning" application remains set until a new profile is started (TRUE).
<hr> Which products are affected?
8400 HighLine with FW < 05.01
What happens?
If during positioning processes with S profiles (bPosDone is set) bPosStop is executed after successful termination of a positioning process, the bPosDone status bit is reset by mistake.
When does the problem occur?
If bPosStop and S profiles are used in table positionings
Possible diagnostics?
Check the bPosDone bit.
Short-term measures / recommendations?
Do not use S profiles.
Evaluation:
The bPosDone bit is often used as a precondition to start a new positioning process. This is no longer a possibility.