Codes of the Inverter Drives 8400 are rounded after download (remedied from V4.5)

Eliminated from:
L-force Loader V4.5

Behaviour of the new version?
The L-force Loader V4.5 transmits codes of the Inverter Drive without any rounding errors.




What is the reaction?
When a code is written, the value of the code will be rounded.

When does the problem occur?
The problem described above occurs in case of codes
- with a factor higher 1 (codes with decimal positions)
and
- either has the data type INTEGER_32 or UNSIGNED_32
and
- to which a value with more than 6 digits is transferred.

Which products are affected?
L-force Loader V4.4
Inverter Drive 8400

Diagnostics options?
None

Short-term measures/recommendations?
Use the L-force Loader V4.5. for download

Evaluation:
The functional restriction may cause rounding errors during the transfer of code values to an Inverter Drive 8400. This function restriction is eliminated with the L-force Loader V4.5.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201002743/1/