Remedied from?
Communication modules Profibus E94AYCPM FW 1.11
Behaviour of the new version?
The correct error code (parameter value cannot be changed) is reported.
Which products are affected?
Communication modules Profibus E94AYCPM FW 1.00, 1.05 and 1.10
What happens?
When a string code is accessed, the error is reported (illegal format), although the error message should be displayed (parameter value cannot be changed).
When does the problem occur?
When an empty string is tried to be written onto a display string code via DP-V1.
Possible diagnostics?
When the error is reported (illegal format), although the error message should be displayed (parameter value cannot be changed).
Short-term measures/recommendations?
None
Evaluation
As of FW 1.11, the correct error code is reported.