Which products are affected?
ECS axis module ECSxx series, operating software ≤ V6.6
What happens?
GDC indicates an error message when executing the reset node command (C0358) via GDC. The error is caused by an undefined response telegram of the ECS.
When does the problem occur?
When executing the reset node command (C0358) via GDC.
Possible diagnostics?
Error message in GDC.
Short-term measures/recommendations?
None.
Evaluation:
The communication connection to the drive may get lost since the reset node is executed. This may happen if e. g. the node address or baud rate has been changed. In this case a following write command cannot be executed via GDC (e. g.: save the parameter set, C0003 = 1). The communication must be re-established.