Undefined signals at encoder connection X8 (master frequency output) (remedied from B-SW V6.5)
Remedied from:
ECS axis module B-SW V6.5
Behaviour of new version?
The master frequency output (encoder connection X8 configured as master frequency output) is now working correctly so that downstream count modules or master frequency inputs of slave drives are able to process the signals correctly.
Which products are affected?
ECS axis module B-SW V3.0
What happens?
The signals at encoder connection X8 (configured as master frequency output) can sometimes not be processed correctly by subsequently connected count modules or master frequency inputs of slave drives.
When does the problem occur?
In some cases if X8 is configured as master frequency output. In most applications this behaviour could not be observed.
Possible diagnostics?
None.
Short-term measures/recommendations?
None.
Evaluation:
Master frequency applications using the master frequency output X8 are affected and can therefore not be implemented. An undefined drive performance of the slave drives occurs.
Published with service message No. 2004/26 and 2004/27