Writing recipes with 64 and more values is not possible (elimination)

Which products are affected?
EVS93xx-EI (Servo PLC Version 6.5 DSMC control board)
EVS93xx-ET (Servo PLC Version 6.5 DSMC control board)
EPL-10200 EI (Drive PLC Version 6.5)

Eliminated function restriction:
Writing recipes with more than 64 values is no longer restricted.
 
Which products are affected?
EVS93xx-EI (Servo PLC Version 6.2 DSMC control board)
EVS93xx-ET (Servo PLC Version 6.2 DSMC control board)
EPL-10200 EI (Drive PLC Version 6.2)

What happens?
When trying to write recipes with 64 and more values, the message window 'The maximum number of variables to be monitored has been exceeded. Please close a window.' appears. This message still appears when all windows have been closed. Therefore, it is not possible to write a recipe consisting of 64 and more values.

When does the problem occur?
When writing recipes with 64 and more values.

Possible diagnostics?
None.

Short-term measures/recommendations?
Do not use recipes with more than 63 values.

Evaluation:
The writing of recipes with more than 64 values is only required for special applications, e.g. friction characteristic selection in winding applications.  

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200406423/1/