Inverter is enabled, but shows no reaction to speed set value

Question:

The 9300 drive controller can be enabled (IMP in the display disappears), but default of speed set value is not possible.

Answer:

The correct wiring of the control terminals must be checked.

In spite of coding the terminals of terminal strip X5 are often exchanged. As the output A 1 and the terminal 28 are opposite, the inverter can be enabled with internal supply of the control terminals. All other connections are, however, assigned incorrectly, so that the drive does not start.