Keypad is working very slowly with 9300 Servo PLC

Question:
Why can the Servo PLC only be operated very slowly from the keypad?

Answer:
The cause of this could be a very long user program which prevents operation of basic functionalities, e. g. reading the keypad, CAN, SDO, AIF-SDO, ...

Remedy:
Via C2100 it is possible to implement a forced change of time slices after a time has elapsed.
Via C2102 it is possible to set the mode of time slice switchover.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/20010104/1/