Fixed as of:
i950 Servo Inverter FW: as of V01.14
Behavior of the new version:
For SDO read operations (parameter communication), unused data bytes in the SDO response telegram are initialized to 0x00. The response telegram contains only the read value and unused data bytes set to 0x00. Data from a previous SDO response telegram is no longer carried over.
Description of the behavior:
When performing an SDO read operation on an index with less than four bytes of payload data, the unused data bytes in the response telegram are not initialized to 0x00. These bytes may contain data from a previously transmitted SDO response telegram. The data length specified in the protocol header and the valid data bytes of the read object are not affected by this.
Under what conditions does this behavior occur?
This behavior occurs during consecutive SDO read operations on objects with different data lengths. If a 32-bit object is read first, followed by an 8- or 16-bit object, the unused data bytes in the second response may still contain data bytes from the previous 32-bit response.
Affected products:
, i950 servo inverter, FW V1.13
Short-term measures / Assessment / Recommendations:
It is recommended that you update the device to one of the firmware versions listed above or a newer, released version. Until the firmware update is installed, only the number of valid data bytes specified in the SDO protocol header may be taken into account when evaluating an SDO response telegram. Unused data bytes must be ignored by the CANopen master or the evaluating application.
[Automatic Translation]