i950 PROFIBUS: Red status LED stays on instead of flashing

     

​Fixed as of:

i950 Servo Inverter FW: starting with V01.15.02 (planned)
Behavior of the new version:
The red “BUS-ERR” status LED indicates the current PROFIBUS error condition using the specified flashing pattern. After the watchdog timeout period has elapsed, the LED flashes. In the event of a PROFIBUS parameterization error, the LED flashes once; in the event of a PROFIBUS configuration error, the LED flashes twice. A continuously lit LED continues to indicate an invalid station address or an unrecoverable error.

Description of Behavior:
When a PROFIBUS watchdog, parameterization, or configuration error occurs, the red “BUS-ERR” status LED remains lit continuously. The different flashing patterns designated for these error conditions are not displayed. Therefore, the actual error condition cannot be clearly distinguished based on the LED display.

Conditions under which the behavior occurs:
This behavior occurs on an i950 with PROFIBUS fieldbus in i950 standard mode when a condition is triggered that should cause the red “BUS-ERR” status LED to blink, flash once, or flash twice. This applies in particular to an expired watchdog timeout, a PROFIBUS parameterization error, and a PROFIBUS configuration error.

Affected products:
i950 Servo Inverter FW

Short-term measures, Recommendations,Assessment:
It is recommended to update the device to the firmware version mentioned above or a newer, approved version. Until the firmware update is installed, the continuously lit “BUS-ERR” status LED must not be used on its own to identify a PROFIBUS error condition. For a definitive diagnosis, the PROFIBUS diagnostic and status parameters or the diagnostic information from the PROFIBUS master must also be evaluated.

[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500417/1/