Fixed as of:
PLC Designer 4.2
Behavior of the new version:
The FAST Motion axis parameters are always written reliably.
Description of the behavior:
When writing the FAST Motion axis parameters from PLC Designer to the controller, the set values (feed constant, gear ratio, etc.) may be lost.
Conditions under which the behavior occurs:
If certain parameters are not modified (for example, Index: 0x512b, Subindex: 92), this causes subsequent parameter blocks to be skipped when the data is written.
Affected products:
PLC Designer (versions 3.24 through 4.1)
Short-term measures, recommendations, assessment:
If a loss of FAST Motion axis parameters is detected, these can be restored in PLC Designer by using the "Clean All" function and then downloading and create boot project.
[Automatic Translation]