Fixed as of:
Behavior of the new version:
Description of the behavior:
If encrypted communication between PLC Designer and the controller is enabled, creating a boot application with a new device name results in the inability to establish a connection after the controller is restarted.
Conditions under which the behavior occurs:
Encrypted communication enabled
Renaming the device while creating a boot application
Affected products:
PLC Designer 4.2
Short-term measures, recommendations, assessment:
Action 1
- Delete the gateway you are using.
- Add the device’s gateway again, and then connect to the device.
- After that, the new certificate can be accepted.
Action 2
- Select another available gateway and use it to connect to the target device.
- This will allow the new certificate to be accepted.
[Automatic Translation]