L_TS2P_FlexCamState: Cam switching in limited measuring system fails (fixed as of V3.33.0)

Fixed as of:
L_TS2P_TechModulesSynchronizingCamming (from V3.33.0)
(Update via Easy Package Manager)

Behavior of the new version;
The L_TS2P_FlexCamState moves the cam disc as desired after a cam disc change.


Description of behavior:
The L_TS2P_FlexCamState technology module moves the cam disc incorrectly after a cam disc change.

Conditions under which the behavior occurs;
Two different cam discs are run through one after the other.

  • After the first cam disc has been traversed, the second cam disc is selected.
  • The resulting x-position calculated from the scaled master position is outside the cam disc.

 
Affected products;
FlexCAM technology module  (L_TS2P_FlexCAMState from library L_TS2P_TechModulesSynchronizingCamming)

Short-term measures, Recommendations, evaluation:
When changing curve writing with an active scaling factor, relative reference between the position of the master axis and the cam disc xMasterAbsolute = FALSE