Outputs on the controller's backplane bus are not set to "0" in the event of a PLC crash (corrected from V1.15.1)

     

Corrected from: 

Cabinet Controller c520 V1.15.1

Cabinet Controller c550 V1.15.1


Behavior of the new version: 

If the PLC Runtime or the controller operating system crashes unexpectedly, all outputs of the I/O modules connected to the controller’s backplane bus are setto "0".

 

Description of the behavior: 

The outputs on the controller's backplane freeze.

 

Conditions under which the behavior occurs: 

In very rare cases, e.g., due to a hardware defect, the PLC runtime or the controller operating system may crash. In this case, the outputs of the I/O modules connected to the controller’s backplane bus permanently retain their last set values.

 

Affected products: 

Cabinet Controller c520 V1.15.1

Cabinet Controller c550 V1.15.1

 

Immediate action, recommendations, assessment: 

The probability of this functional limitation occurring is very low. Regardless, the behavior of the outputs must be taken into account when configuring the machine.
[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202600090/1/