L_IE1P_SetError: i950 does not support the severity 'Fault'

Corrected from:
-
Behavior of the new version:
-


Description of behavior:
If an error is triggered via the function module L_IE1P_SetError or L_IE1P_SetErrorSingle, the reaction set at the eReaction input is executed, but the message:

  • can no longer be acknowledged
  • cannot be diagnosed via FB L_IE1P_ReadActualError or object 0x2010

Conditions under which the behavior occurs:
The Severity 'Fault' [30] is not fully supported by the Servo Inverter i950. If an event with this severity is triggered via the function block L_IE1P_SetError or L_IE1P_SetErrorSingle, the behavior described above can be observed.

Affected products:
Library L_IE1P_ApplicationErrors

Servo Inverter i950


Short-term measures, Recommendations, evaluation:
Do not use the severity 'Fault' [30] in the PLC program for a servo inverter i950. 

[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202300393/1/