Error messages when compiling a project for 'i950 Extended for customer-specific devices only'

Corrected from:

This issue cannot be resolved in PLC Designer.

Starting with the i950 B and firmware version V2.0.3,
PLC Designer version 4.0.1 or later can be used.


Description of behavior:

When compiling a project in PLC Designer, compiler errors occur that refer to “visuelembase, 4.8.0.0” and/or “CmpEventMgr_Interfaces...”.


     

Conditions under which the behavior occurs: 

The compiler error messages occur when the following conditions are met:

  • The PLC device is an i950 A with firmware version lower than V2.x.
  • The device description “i950 Extended for customer-specific devices only” is selected.
  • A CODESYS WebVisu is an object of the PLC device.
  • The version of PLC Designer being used is V4.0.1.

Background:

Starting with PLC Designer V4.1.x, newer Visu packages (V4.8) are used, which are only supported by a runtime version in the i950 starting with V2.

This results in the following dependencies:

  • For i950 A with firmware V1.x, PLC Designer V4.0.1 must be used (or PLCD V3.x for older projects).
  • For i950 B with firmware V2.0.3 or later, PLC Designer V4.1.0 or later can be used.



Affected products: 
PLC Designer V4.1.0

Short-term measures, recommendations, evaluation: 
Continue to edit affected projects with a PLC Designer version ≤ V4.0.1.