Error messages during translation: Unknown type: '...' (corrected from V4.0)

Corrected from:
PLC Designer V4.0
Behavior of the new version;
The compiler version is set correctly by default.


Description of behavior;
Various error messages occur when compiling the PLC project;

C0077; Unknown type; 'L_IMHP_ModuleHandler'
C0077: Unknown type: 'L_IMHP_IModuleHandler'
C0077: Unknown type: 'L_MC1P.L_MC1P_DataManager'
...

Conditions under which the behavior occurs;

The behavior described above occurs when a new project is created with PLC Designer based on the standard project for an i950 servo inverter with firmware version V1.10.x.

Affected products:
PLC Designer V3.28

Short-term measures, Recommendations, Evaluation:
When creating the project, the wrong compiler version is preselected for the i950 servo converter with firmware V1.10. 

When creating a new PLC project, make sure that the current compiler version V3.5.17.40 is set in the 'Standard Project' dialog and correct it manually if necessary.

It is also possible to change the compiler version retrospectively. To do this, set the fixed version of the compiler to 3.5.17.40 in the 'Compile options' category of the 'Project Settings' dialog (menu 'Project' > 'Project Settings').

The L_FAST_xxx project templates are not affected by this functional restriction.

[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202400284/1/
Kontaktformular