OPC UA mapping - Space in base model name => Compiling error

     

Fixed from: 
V4.1

Behavior of the new version: 
The input of the file name is checked and a pop-up is displayed if the input is invalid.

Description of the behavior:
If there is a space in the name of the basemodel that was imported, then there is a compiler error when compiling. Unfortunately, the error information gives no indication of the cause.

Conditions under which the behavior occurs:
=> Space in basemodel name

Affected products:
PLC Designer version V4.0 and higher

Short-term measure, recommendations, evaluation:
Remove spaces from the basemodel name and then import this basemodel before the basemodel with the space in the name has been deleted. Then have PLC Designer translate the project.


URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500387/1/