Controller with Profinet: PDO data is not sent from the controller to Siemens PLC (fixed from V1.13.0)

Fixed as of:
Controllers c5xx and c430 (from FW V1.13.0)

Behavior of the new version;
Free choice of modules for the configured PDO mapping


Description of behavior;

The process data from the Lenze controller is not sent to the SIEMENS IO controller.

Conditions under which the behavior occurs;

  • If the first slot configured in the Lenze controller for the fieldbus device consists of a pure input or output module, an error occurs.

Affected products:
Controller C5xx
Controller C430


Short-term measures, Recommendations, evaluation:
Use of a combined in/out module in the first slot of the fieldbus participant in the Lenze controller.

[Automatic Translation]