i950ES / i750ES / i750AS: Loading the factory setting does not affect parameter 0x28E8:01..02 "Diagnostic: Config. diagnostic value 1 & 2" (no change planned)
Removed from:
i950 Extended Safety (ES): No change is currently planned. i750 Extended Safety (ES): Currently no change is planned. i750 Advanced Safety (AS): No change is currently planned.
Description of the behavior: Executing the device command "Load default" (0x2022:01), results in the following parameters not for resetting to factory settings:
"Diagnosis: Config. Diagnostic value 1" - 0x28E8:01
"Diagnosis: Config. Diagnostic value 2" - 0x28E8:02
Under what conditionsdoes the behavior occur?
The configuration of the diagnostic values 1+2 in the objects 0x28E8:01..02 are not parameterized equal to the factory setting.
The device command "Load default" (0x2022:01) is executed or the "Reset device" button is pressed via the tool interface in the Easy-Starter.
Short-term measures / Assessment / recommendations: The desired default values can be written 'manually' in 0x28E8:01 and 0x28E8:02. Athen the parameter set must be saved again in the device.