Use of text lists leads to error message during project download

Corrected from:
-

Behavior of the new version:
-


Description of the behavior:
When logging in (downloading the PLC project), a dialog opens with the message:

Error downloading:
2 unresolved references...

The messages appear in the PLC Designer message window:

[FATAL ERROR]   Unresolved reference: 'DYNAMICTEXTUNREGISTERFILE'
[FATAL ERROR]   Unresolved reference: 'DYNAMICTEXTREGISTERFILE' 

Conditions under which the behavior occurs:
When logging into a Lenze Controller c430, the error messages described above may appear if the 'Text List' object is used in the PLC project.

Affected products:
PLC Designer from V4.0
Cabinet Controller c430 from V1.14

Short-term measures, Recommendations, Rating:
Open the 'Text list' tab in the properties of all 'Text list' objects and set the 'Download by' field to the value 'Visualization'. The project download should then be possible without errors.

PLC Designer_TextListDownloadby_SSHOT.png

The Lenze Controller c520 and c530 are not affected by this functional restriction.