Question:
Due to a wiring error, my
w590-C-2B/3E-001 module has an active error. How can I reset it?
Answer:
Errors at the safe inputs and outputs (.e.g. cross connection,
incorrect test pulse, discrepancy, undercurrent, ...) can be reset by a short signal
at the reset input on the respective FSoE master FB. It is
It is not necessary to switch the supply voltage. The AutoReset input
of the FSoE master FB must not be connected.