PROFINET process data communication does not work (fixed with V1.13)

Corrected from:
Cabinet Controller c430 V1.13
Cabinet Controller c520 V1.13
Cabinet Controller c550 V1.13
Behavior of the new version:
There exists no restriction in the choice of the PDO.


Description of the behavior:

  • No process data is exchanged between the higher-level controller and the Lenze controller via PROFINET.
  • The higher-level controller reports that no PDO slot is available in the PROFINET slave (Lenze controller).

Conditions under which the behavior occurs:
The behavior described above occurs when an input-only or output-only slot is used in the first slot of the PROFINET PDO configuration:

  • Slave-In / Master-Out...
or
  • Slave-Out / Master-In...
Affected products:
Cabinet Controller c430
Cabinet Controller c520
Cabinet Controller c550

Short-term measures, Recommendations, Rating:
Use the slot 'Mixed In/Out...' as the first slot in the PROFINET PDO configuration. After the slot, the configuration can be executed as originally planned.


[Automatic Translation]