L_IE1P_ReadActualtSeverity: FB does not display the warning of a drive (corrected from V3.30.0)

​

Corrected from:

Library L_IE1P_AppllicationErrors (from V3.30.0)

 

Behavior of the new version:

A drive controller warning is also displayed in the FB L_IE1P_ReadActualSeverity.



Description of the behavior:

The FB L_IE1P_ReadActualtSeverity is used to read the current severity of a motion axis (incl. the assigned drive).

If a warning is active in the drive assigned to the motion axis, this will not be displayed in the FB L_IE1P_ReadActualtSeverity. 

 

Conditions under which the behavior occurs

There is a warning in the drive. 

 

Affected products:

Library L_IE1P_AppllicationErrors

Cabinet Controller c520
Cabinet Controller c550

Short-term measure, recommendations, evaluation:

The presence of a drive warning can be checked via the status output of the FB L_MC1P_AxisBasicControl(V2) function block or the equivalent status structure on the technology module.

[Automatic translation]



URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202300184/1/
Kontakt