The Safe Muting function deactivates safe inputs or functions of the safety bus. The deactivation is limited to a maximum of 30 minutes. It can be cancelled or stopped at any time. A special muting password must be entered for this purpose. The safe inputs or functions that are to be hidden during Safe Muting must be selected beforehand via the safe parameterisation.The Safe Muting function can only be activated via the Lenze Safety Parameter Editor.
New parameters for safe muting are :
0x213A:1-5 Hide muting sources
0x213B:0 Display muting remaining time
0x213C:0 Set output "Muting active
Contained in which products? i950 - Extended Safety (ES): from V01.01.01.0000
Usage:
The Safe Muting function may only be used during commissioning or for maintenance work. It is used to move the motor even if the inverter is in a safe state.