i950 ES: Function Safe Muting (from V01.01.01)

Function extension:

The Safe Muting function deactivates safe inputs or functions of the safety bus. The deactivation is limited to a maximum of 30 minutes. It can be cancelled or stopped at any time. A special muting password must be entered for this purpose. The safe inputs or functions that are to be hidden during Safe Muting must be selected beforehand via the safe parameterisation.The Safe Muting function can only be activated via the Lenze Safety Parameter Editor.

New parameters for safe muting are : 
  • 0x213A:1-5 Hide muting sources
  • 0x213B:0 Display muting remaining time
  • 0x213C:0 Set output "Muting active

Contained in which products?
i950 - Extended Safety (ES):   from V01.01.01.0000

Usage:

The Safe Muting function may only be used during commissioning or for maintenance work. It is used to move the motor even if the inverter is in a safe state.