Unresolved reference 'DYNAMICTEXTITERATEINDICES' (fixed as of V3.20.1)

Corrected from:
Cabinet Controller c300 V3.20.1
Cabinet Controller 3200C V3.20.1
Panel Controller p500 V3.20.1

Response of the new version:
A project with web visualisation can be successfully downloaded into the Lenze controller with firmware version 3.20.1 using the current version of compiler, visualisation profile and visualisation style.

What happens? 
During the PLC project download, the following error message appears in the message window of the PLC Designer:
Unresolved reference: 'DYNAMICTEXTITERATEINDICES'
 
The PLC project cannot be transferred to the controller.

When does the behaviour occur?
The error message can occur when using the CODESYS web visualisation, if versions greater than or equal to V3.5.15 for
  • the compiler (menu 'Project' > 'Project Settings', category 'Compiler options'),
  • the visualisation profile (menu 'Project' > 'Project settings', category 'Visualization Profile') and
  • the visualisation style (object 'VisualizationManager', Style Settings).
are set.
 
Which products are affected? 
Cabinet Controller c300 with CoDeSys WebVisualisation
Cabinet Controller 3200C with CoDeSys WebVisualisation
Panel Controller p500 with CoDeSys WebVisualisation

Short-term measures:
Set the above components to versions < V3.5.15.
 
Evaluation / recommendations:
The download of a PLC-Designer project for a Lenze controller with CODESYS Web-Visualisation aborts with an error message. An applicative solution is described under 'Short-term measures'.

Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202100092/1/