Corrected from:
Cabinet Controller c300 V3.21.2
Cabinet Controller 3200C V3.21.2
Panel Controller p300 V3.21.2
Panel Controller p500 V3.21.2
Response of the new version:
After changing the time zone via parameter C92, this parameter is displayed correctly except when C92 is set to the following time zones:
- Cape Verde Standard Time
- Mid. Atlantic Standard Time (=Middle East Standard Time)
What happens?
When setting some time zones, e.g. 'Russian Standard Time', the parameter C92 is then displayed in red.
When does the behaviour occur?
The behaviour occurs when setting some time zones via WebConfig. It is a display problem. Despite the red display of the parameter, the selected time zone was set correctly.
Which products are affected?
Cabinet Controller c300 from V3.8
Cabinet Controller 3200C from V3.0
Panel Controller p300 from V3.8
Panel Controller p500 from V3.2
Short-term measures:
Use the EASY Starter to set and display the time zone.
Evaluation / recommendations:
When setting the time zone via parameter C92 of the controller, this is displayed in red, which typically happens if the value was not accepted by the controller. The function restriction concerns the WebConfig of the controller. The time zone can be set successfully with the EASY Starter.
Automatic Translation