Error message 'Error writing parameter 0x500A:054' during parameter set download (fixed as of V3.20.1)

Corrected from:
Cabinet Controller c300 V3.20.1
Cabinet Controller 3200C V3.20.1
Panel Controller p300 V3.20.1
Panel Controller p500 V3.20.1

Response of the new version:
The EASY Starter can be used to transfer a parameter set via a Lenze controller as a gateway to an i950 servo inverter without errors.
 
What happens? 
When downloading a parameter set to an i950 servo inverter, the error message appears:
Error writing parameter 0x500A:054

When does the behaviour occur?
The error message occurs when an attempt is made with the EASY Starter to carry out a parameter set download via a Lenze controller as a gateway to an i950 servo inverter.
 
Which products are affected? 
Cabinet Controller c300
Cabinet Controller 3200C
Panel Controller p300
Panel Controller p500

Short-term measures: 
After downloading the parameter set, check the affected parameter 0x500A:054 (= Following error: Monitoring enabled) and set it again if necessary. Then save the parameter set in the Servo Inverter i950.
 
Evaluation / recommendations:
When transferring a parameter set to an i950 servo inverter through a Lenze controller, the parameter 0x500A:054 cannot be written to. An error message appears. The parameter must be subsequently changed and saved in a power-failure-proof manner. 