c5x0 / c750: Profinet: sporadically the station name is lost after power switching

What happens?
The stored station name for PROFINET is not set after a restart, so that commissioning is performed by the
PROFINET master (IO-Controller) cannot take place.
 
When does the behaviour occur?
The station name is configured and saved via TIA Portal.
 
Which products are affected?
Cabinet Controller c5x0 
Cabinet Controller c750

Short-term measures:
After changing the station name via TIA Portal, the parameter set of the C5x0/C750 must be saved afterwards.