i950 ES: Activation of the safe parameters after *.lda transfer not possible (corrected from V01.02.03)

Corrected from:
i950 Extended Safety:  from V01.02.03.00
 
Response of the new version:
After a complete device application has been transferred to a device using the Application Loader or Easy Starter, the safe parameter set is transferred correctly.
The safe parameter set is active after the release information about the safe parameter list has been generated.
The parameterized safety functions can be executed.

 
What happens?
After transferring a complete device application (*.lda file including safe parameters) via a Lenze tool (application loader, easy starter), the safe parameter set cannot be activated and released by generating the release information.
The safe parameter set cannot be activated and released by generating the release information.
The safety option reports an error after checking the safe parameter set (0x2A00638C).
 
When does the behaviour occur
The behaviour occurs if the safe parameter set is not transferred directly to the device via the Lenze tool with the safe parameter list.
 
Which products are affected?
i950 Extended Safety
 
Short-term measures / Evaluation / Recommendations:
Transfer the safe parameter set directly to the drive controller using a Lenze tool.
During parameter set transfer, the release information is generated directly and the safe parameter set is activated immediately.
 
Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201900401/1/