Trace recording does not start automatically after a restart (corrected from c5xx V01.03.00 and i950 FW from V01.04.01)

Corrected from:
Controller c520 from V1.3
Controller c550 as from V1.3
Servo inverter i950 FW:  from V01.04.01.1471

Response of the new version:
If the 'Automatic restart' switch is set in the 'Trace configuration' dialog, the trace recording starts automatically after a restart of the controller/drive.
 
What happens?
Although the 'Automatic restart' switch is set in the 'Trace configuration' dialog, the trace recording does not start after a restart of the controller.
 
When does the behaviour occur?
The behavior always occurs if the 'Automatic restart' switch is set and the controller is restarted.
 
Betroffene Produkte:
Controller c520 from V1.1
Controller c550 from V1.1
Servo Umrichter i950 FW
 
Short-term measures, Evaluations/Recommendations:
No short-term measure available.
The 'Automatic restart' function is required for long-term measurements in which the controller is also switched off or for measurements in which the event occurs immediately after switching on.
 