i950 ES: Incorrect triggering if several functions are parameterised on a safe digital input (corrected from V01.01.01)

Corrected from:
i950 Extended Safety (ES): as of V01.01.01.0000

Response of the new version:
The function restriction described below has been eliminated.
 
What happens?
The safety function is not effective on request.

When does the behaviour occur?
The safety functions OMS, RMS and ES are affected if they are configured for a safe digital input in combination with another safety function.

Which products are affected?
i950 Extended Safety (ES)
 
Evaluation / Short-term measures:
For devices with firmware V01.00.xx the above mentioned combination of functions must not be used.
The functions OMS, RMS and ES must each be assigned to their own safe digital inputs.
A software update in the field is not possible.
If device replacement is necessary, please contact the Lenze helpline at +49 5154 82 2222 or clearing@Lenze.com.