PROFINET PROFIdrive multi-parameter access: only 32 instead of 40 parameters simultaneously (fixed from V01.02)

Corrected from:
Cabinet Controller c550 from firmware V01.02.00.960
Response of the new version:
The described behavior no longer occurs.
What happens?
Instead of 40, only 32 parameters could be read back by Profidrive with a multi-parameter access.
When does the behaviour occur? 
If more than 32 parameters are requested by multi-parameter access.
Which products are affected? 
Cabinat Controller c550
Short-term measures:
 -
Evalution/Recommendations:
Maximum number of 32 parameters with multiparameter access