Deactivating manual acknowledgement for WarningLocked

Function extension:
When setting C00143 bit 4 = 1 (Warning instead of WarningLocked), errors with the error response WarningLocked no longer need to be acknowledged manually. As soon as the cause of the warning has been removed, the warning will be reset automatically and the red LED will go off.


Contained in which products?

  • Inverter Drives 8400 motec

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201900122/1/