SLVC/VFC: Apparent current display C054 jitters at f = 0 Hz

Corrected from:

Inverter Drives 8400 StateLine, HighLine, and TopLine from firmware version 14.00.00.00

Response of the new version?

The jitter of the apparent current has been suppressed for f=0 Hz (in SLVC/VFCplus mode).

Which products are affected?

Inverter Drives 8400 StateLine, HighLine, and TopLine with a firmware version lower than 14.00.00.00

What happens?

The apparent current display C054 jitters from 0 A to magnetising current.

When does the problem occur?

Only for SLVC and VFCplus: at output frequency 0 and deactivated auto-DC-injection braking,

the apparent current display C054 jitters from 0 A to magnetising current.

Short-term measures/recommendations?

None

Evaluation:

This is a display error. The process signals of the apparent current are processed correctly. Therefore the control mode is not affected.

If code C054 is evaluated via a PLC, this may cause an error.


URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201500653/1/