Corrected from:
Inverter Drives 8400 StateLine from firmware version 13.04.00.00 Inverter Drives 8400 HighLine and TopLine from firmware version 14.00.00.00
Response of the new version?
After a parameter set changeover, the parameters from the "Definable parameter list" with a connection to the "Motor data parameter list" are only converted when the codes of the "Motor data parameters" have updated the values.
Which products are affected?
Inverter Drives 8400 HighLine and TopLine with a firmware version lower than 14.00.00.00
Inverter Drives 8400 StateLine with a firmware version lower than 13.04.00.00
What happens?
Parameters are calculated incorrectly. This can have the effects that the drive behaviour deteriorates or the motor does not start.
When does the problem occur?
After a parameter set changeover of parameters which are connected to the motor control and which are switched over via the "Definable parameter list".
Short-term measures/recommendations?
Integration of additional parameters into the user-definable parameter change-over function, so that parameters with a connection to the motor control only rank second in the list.
Evaluation:
If parameter sets are changed over with a change-over of the motor data parameters, the motor should be brought to a standstill before.