Motor parameter identification at switching frequency of 8kHz

Which products are affected?
Inverter Drives 8400 StateLine, HighLine, and TopLine from firmware version 14.00.00.00

Functional description
By means of code C2864/1 bit4, a motor identification with a switching frequency of 8 kHz can be set.
This adjustment of the switching frequency is required for specific motors and motor filters.
It is advisable to switch over to 8kHz if the motor and/or motor filter is/are not suited for chopper frequencies < 8kHz.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201500606/1/