Incorrect unit of L_SRFG inputs in FB Editor display

Corrected from: 

  • Inverter Drives 8400 HighLine V16.00.00
  • Inverter Drives 8400 TopLine V16.00.00


Response of the new version:

From Engineer 2.22 and 8400 V16.00, the unit of the L_SRFG inputs is correctly displayed in [%] in the FB Editor.

SRFG_korrigiert.jpg 


 
What happens?
In the FB Editor, the inputs of the L_SRFG are not displayed in the expected unit [%] but in [inc] online.

SRFG_falsch.jpg 

When does this behaviour occur?
The behaviour occurs when carrying out an online diagnostics in the FB Editor using the known firmware versions and Engineer versions lower than V02.22.

 

Which products are affected?

  • Inverter Drives 8400 HighLine < V16.00.00, in the Engineer lower than V02.22
  • Inverter Drives 8400 TopLine < V16.00.00, in the Engineer lower than V02.22

 

Short-term measures:

Manual conversion of the displayed value: 16384 corresponds to 100% 

 

Evaluation/recommendations:

  • Misleading diagnostics
  • The incorrect display does not have any influence on the block function

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201500463/1/