AIF interface codes do not have any effect or are always 0 (eliminated from Drive PLC V8.5)

Eliminated from:
EPL-10200 (Drive PLC V8.5)

Behaviour of the new version:
The restriction of the codes has been eliminated.



Which products are affected?
EPL-10200 (Drive PLC V8.4 and lower)
ECSxA (ECS axis module V8.4 and lower)
9300 Servo PLC V8.4 and lower

What happens?
It can be observed that the display codes for the AIF interface responds as follows:
2355/1..6 (AIF-CAN: System bus identifier for PDOs) are always 0
2356/2 (AIF-CAN: Time setting)has no effect
2359/0 (AIF-Module DIP-switch position) is always 0
2375/1 (AIF-CAN: TX-Mode for XCANx_OUT) has no effect, transmission is always effected in a sync controlled way

When does the problem occur?
The behaviour occurs if the above-mentioned codes of the AIF interface are used.

Possible diagnostics?
None.

Short-term measures/recommendations?
None.

Evaluation:
The function restriction only affects the above-mentioned codes of the AIF interface.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201205129/1/