New code for displaying the active IP parameters

Which products are affected?
E94AYCER communication module firmware version 1.40

Function description
The active IP address can differ from the contents of code C13000 / C14000 depending on the situation if the station name has been changed via field bus or parameter before. The selection of the IP address via Profinet master or Lenze Profinet configurator in the Engineer ALWAYS becomes effective immediately. However, if an IP address is selected via code C13000 / C14000 the address does not become effective in the module before the next mains switching has been executed.
C13010 or C14010: IP address
C13011 or C14011: Subnet mask
C13012 or C14012: Standard gateway

Applications
The Profinet communication is based on a TCP/IP communication in case of which both, producer and consumer, have an own IP address.