Parameter change-over - Error when editing the list of change-over parameters by means of Engineer 2.13 and 2.14

Eliminated from:
...

Behaviour of the new version?
...



Which products are affected?
Engineer 2.13 (incl. SP1 and SP2) and Engineer 2.14
8400 StateLine, HighLine and TopLine
8400 protec HighLine and StateLine

Not affected: 8400 motec!

What happens?
If the 'LS_WriteParamList' system block is used the list of parameters to be changed over can be defined via the 'Parameter change-over' Engineer dialog which can be accessed via the 'Application parameter' tab and via the Function Block editor.  
The four different values of the change-over parameters get lost when using this Engineer dialog for editing purposes.

When does the problem occur?
The values defined before get lost if change-over parameters are added or deleted.

Possible diagnostics?
The change-over parameters are reset to Lenze default setting after the list has been edited.

Short-term measures/recommendations?
Edit the list (add, delete) only via the parameter list on the 'All parameters' tab.

Evaluation:
The defined values are not available anymore after some kind of editing has been carried out. Thus, the function responds differently than expected.
If the list has been edited the result can immediately be seen in the overview.

Search terms: Parameter set change-over

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201105579/1/