Display codes are not reset when the application data download has been aborted (elimination)

Behoben ab:
Eliminated from:
EVS93xx-EI (Servo PLC V8.0)
EVS93xx-ET (Servo PLC V8.0 with technology function)

Behaviour of the new version?
If the application data file has not been completed sucessfully the PLC target system resets the following codes:
C2130 = no Add-Data
C2131 = 65535
C2132 = 0
C2133 = 0



What happens?
Incorrect information is displayed in the following codes:
C2130 DIS:  Add data file name (Appl.-Flash)
C2131 DIS: Add data file type (Appl.-Flash)
C2132 DIS: Add data file version (Appl.-Flash)
C2133 DIS: TimeStamp Add-Daten (Appl.-Flash)

When does the problem occur?
The codes mentioned before are not reset if the download of the application data file has failed (lc9 file = CAM data file).

Which products are affected?
EVS93xx-EI (Servo PLC V7.2 and lower)
EVS93xx-ET (Servo PLC V7.2 and lower with technology function)

Possible diagnostics?
If the download of the application data file has failed, the PLC target system indicates this by means of a trip message. Check if one of the following system error messages is indicated in code C0168/1 after the download:
250 2.Flash Err (Access not possible)
251 AddData CsErr (Checksum error when loading data into the FLASH memory)
252 AddData DIErr (Error when downloading data into the FLASH memory)

Short-term measures/recommendations?
Repeat the download of the application data file.

Evaluation:
If the application data download has failed the correspondig display codes are not reset. Trip 232 (= Add data not available (CAM data)) is triggered.