LS_WriteParamList provides inconsistent data (eliminated from V5.0 onwards)

Eliminated from:
StateLine / HighLine with firmware version V05.01 or higher

Behaviour of the new version?
The parameter change-over can be carried out as defined by the table of the LS_WriteParamList system block.



Which products are affected?
8400 StateLine / HighLine with FW < 05.01

What happens?
When changing over between two parameter lists, some of the parameter values from the last active list remain and some of the parameter values from the newly activated list are transferred.

When does the problem occur?
If the parameter change-over is carried out while code write requests are processed.

Possible diagnostics?
The active parameter values are from different parameter lists.

Short-term measures / recommendations?
Do not change the inputs of the change-over / do not request a new data list while the write requests are being processed.

Evaluation:
The error can be avoided if the recommendations are followed.

Information taken from chapter 1.1.49 of Service Message No. 16/2010.