Incorrect setpoint control while approaching the hardware limit switches (eliminated from V5.0 onwards)

Eliminated from:
HighLine with firmware version V05.01 or higher

Behaviour of the new version?
When a hardware limit switch is approached, the configured response is triggered (e.g. Warning).
If firmware version V05.01 is used, the drive may not stop anymore if the hardware limit switch is approached (depending on the configuration of the response to the hardware limit switch (C0595)).



Which products are affected?
8400 HighLine with FW < 05.01

What happens?
The drive is ramped down to a standstill when a hardware limit switch is approached, regardless of the set error response to the hardware limit switch (even if it is set to Warning).

When does the problem occur?
The problem always occurs when a hardware limit switch is activated.

Possible diagnostics?
Configure the response to the hardware limit switch to Warning and trigger.

Short-term measures / recommendations?
None

Evaluation:
The drive stops unexpectedly when the hardware limit switches are reached.

Information taken from chapter 1.1.32 of Service Message No. 16/2010.