Plausibility check

Function description
The default value of the 'OMS: Motion function' was changed from 'SLS1' to 'Free traversing'.
If the SM301 is used without safe speed detection the parameter has to be changed manually up to now although the operating mode changeover has not been used at all. If the parameter has not been changed the plausibility check failed. It was not possible to download the safe parameter set into the 9400.
Now, the monitoring of the safe max. speed only needs to be deactivated (parameter 'SMS: Max. speed Nmax'). This has not been changed intentionally in order to ensure that the commissioner consciously deals with safe parameter setting before the motor can move for the first time.

Included in which products/versions?
Safety module SM301 V1.4

Applications
Applications in which the SM301 is used without safe speed detection.

Information taken from chapter 2.1.4 of Service Message No. 33/2010.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201014118/1/