Process data monitoring does not work in the case of 12 MBaud (remedied from V1.20)

Remedied from:
Communication module Profibus E94AYCPM FW 1.20

Behaviour of the new version?
Process data monitoring works perfectly at 12 MBaud with the new version.



What happens?
At a baud rate of 12 MBaud, it is possible that the set process data monitoring function does not trigger correctly in the event of an error/fault.

When does the problem occur?
The problem occurred only at a baud rate of 12 MBaud.

What products are affected?
Communication module E94AYCPM ≤ FW 1.11

Possible diagnostics?
If process data monitoring no longer works properly, the red BE LED of the module does NOT go out after process data communication has been restored.

Short-term measures/recommendations?
None

Evaluation:
At a baud rate of 12 MBaud, it is not possible to ensure that process data monitoring functions correctly. Error diagnosis is therefore only possible to a limited extent.