Loading the default setting for the OPERATING SYSTEM and processing the code initialisation list for the application software with C0002=2 (ECS as of OPERATING SYSTEM V8.3, SPLC as of V8.0, DPLC as of V8.3)

Function extension
Code C0002 'Load default setting' has been extended to include the selection C0002=2:

C0002 = 1:  Initialise codes for the operating system software with Lenze setting. This setting does not process the codes initialisation list for the application software.

C0002 = 2:  Initialise codes for the operating system software with Lenze setting and process the code initialisation list for the application software. Thus, the initialisation settings of the application are set for the selected codes of the operating system software.

Note for ECS and Drive PLC:
The new selection C0002=2 is not implemented in the current *.pdb device description files for GDC and DDS. Therefore, this new function is not supported by the GDC and DDS PC tools.
Workaround:
Entry via keypad, write selection C0002 = 2 using L_ParWrite() or via interface.

Applications
It has so far only been possible to initialise to a value which does not correspond to the default setting when the applicaiton has been downloaded with the DDS system and user codes. These code values can be set via the code initialisation values DDS dialog.
In addition to the DDS download the code initialisation values can now be loaded with C0002=2.

Included in which products/versions?
ECS Application OPERATING SYSTEM as of V8.3
EVS93xx-EI (Servo PLC) as of V8.0
EVS93xx-ET (Servo PLC with technology function)  as of V8.0
EPL-10200 (Drive PLC) ab V8.3


Published with Service Message No. 2010/32, 2011/02 and 2011/31