Incorrect display of the DFOUT frequency in C13071 or C14071 if C00100 ≠ 16 (remedied from V8.0)

Eliminated from:
9400 HighLine Firmware Version V08.00.24.00

Behaviour of the new version?
Codes C13071 / C14071 display the correct frequency of DFOUT even if C00100 ≠ 16.



Which products are affected?
9400 HighLine Firmware Version ≤ V07.01.06.00

What happens?
Codes C13071 / C14071 (display of the frequency at DFOUT) display an incorrect frequency if C100 ≠ 16.

When does the problem occur?
If a digital frequency module is used in MX1 or MX2.

Possible diagnostics?
Comparison of the code values and the expected value.

Short-term measures/recommendations?
None

Evaluation:
The behaviour usually shows during commissioning but cannot be avoided.
The code displays cannot be used if C00100 ≠ 16. Since they are just display codes, the drive behaviour is not affected.

Published in Service Message No. 26/2010