Process data from the Profibus Master do not arrive at the 9400 Servo Drive basic device (remieded from V2.12 SP1)

Eliminated from:
Engineer HighLevel and Statelevel version 2.12 SP1

Behaviour of the new version?
Due to the new Profibus catalog for Engineer 2.12.1 the process data communication works without problems in both directions.



Which product are affected?
Engineer HighLevel and StateLevel version 2.12
E94AYCPM Profibus communication module, firmware > 1.10

What happens?
The Profibus communication works without problems but the process data from the Profibus Master are not read into the 9400. The process data from the 9400 to the Profibus Master are sent correctly to the bus.

When does the problem occur?
The problem occurs in combination with Engineer 2.12 and Profibus communication module equipped with firmware > 1.10.

Possible diagnostics?
The display codes C13851 / C14851 'All words from the master' and C13852 / C14852 'All words to the basic device' of the Profibus module indicate the correct process data words from the Profibus Master but no process data words arrive  internally at the connected ports.

Short-term measures/recommendations?
Please exchange the Profibus catalogue E94AYCPM_V0111.xml which located in the following directory: C:\...\EngineerHL_2_12\Catalogs\Engineer\ProfibusModule9400\DescriptionFiles by the 'replacement' catalogue provided in the following.

Download:
E94AYCPM_V0111.zip (4 kB): Profibus Catalog for Engineer 2.12

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201007452/1/